...
Email
HOME > Power Relay > RUB General Purpose Relay
RUB General Purpose Relay
RUB General Purpose Relay

RUB General Purpose Relay

Features

The RUB Universal Relay is a 2-pole or 3-pole contactor that can handle load currents up to 10 amps. The relay integrates a non-polar LED for easier coil identification. In addition, there is a lockable test button and inspection window for easy testing and debugging. The relay is also RoHS compliant.

certificate Request A Quote

Share Our Social

RUB General Purpose Relay Details

  • Available in 2 poles and 3 poles.
  • Contact load up to 10A.
  • With non-polarity LED integrated into the relay.
  • Equipped with a lockable test button and inspection window.
  • Identification of coils through test button color.
  • Conformity with RoHS Directive.

RUB General Purpose Relay

RUB general purpose relay consists of a relay and socket. The control voltage range can be extended using a matching socket. It can be used with the following types of sockets: SUB08-E socket, SUB11-E socket, SUB08-A socket and SUB11-A socket.

Characteristics

Contact Configuration 2C 3C
Rated current/ Resistive load 10A/250VAC 30VDC (resistive RES); 7A/250VAC 30VDC (perceptual GEN)
Switching capacity (resistive)  2500VA, 300W
Initial contact resistance ≤50mΩ
Material Ag alloy
Electrical durability ≥10 x 104 (1800 Ops/h)
Mechanical durability ≥2000 x 104 (18000 Ops/h)
Pick-up voltage (23℃) ≤80%
Drop-out voltage (23℃) DC:≥10% (rated voltage),AC:≥30% 50/60Hz (rated voltage)
Maximum voltage (23℃) 110% (Rated voltage)
Insulation resistance ≥100MΩ (500VDC)
Coil operating power DC (W) approx. 1.5
AC (VA) approx. 2.7
Operate time (at nominal voltage) ≤30ms
Release time (at nominal voltage) ≤20ms
Initial breakdown voltage Between open contacts 1000VAC/1min (leakage current 1mA)
Between poles 2500VAC/1min (leakage current 1mA)
Between contacts and coil 2500VAC/1min (leakage current 1mA)
Insulation
characteristics
IEC 60664 UL840
Rated voltage 250VAC
Pollution level 3
Overvoltage level III
Impulse withstand voltage (waveform: 1.2/50us) 4000V
Protection level IP50
Storage temperature/ humidity -55~+85℃/ ≤85%RH (18 months)
Working temperature/ humidity -25~+55℃/ 5%~85%RH (No condensation)
Air pressure 86~106KPa
Shock resistance 10G (half-sine shock pulse: 11ms)
Vibration resistance 10~55Hz double-amplitude:1.0mm
Mounting Plug in
Unit weight approx.85g

Coil Specifications (23℃)

Nominal voltage V.DC 6 12 24 48 110 220
Coil resistance Ω 23.7 96 430 1640 7360 29500
Nominal voltage V.AC 6 12 24 36 48 115
Coil resistance Ω 3.9 17 62.5 144 305 1250
Remarks: Coil resistance: under coil voltage 110V are measured with tolerance of ±10%Ω, above 110V with tolerance of ±15%Ω.

Contact Specification

RUB General Purpose Relay Contact Specification

RUB General Purpose Relay

Dimensions (mm)

RUB General Purpose Relay Relay Kit Dimensions (mm)

Wiring Diagrams

RUB General Purpose Relay Wiring Diagrams

Contact Us

Applicable socket

SUB08-E & SUB11-E Socket

SUB08-E & SUB11-E Socket

relay base for RUB relay,screw type,Din-rail mounting

View The Product Request A Quote
SUB08-A & SUB11-A Socket

SUB08-A & SUB11-A Socket

SUB08-A & SUB11-A socket for RUB relay.

View The Product Request A Quote

You might also be interested in the following products

RKL Miniature Power Relay

RKL Miniature Power Relay

general power relay, plug in pin, 1 pole 16A and 2/...

View The Product Request A Quote
REH Power Relay

REH Power Relay

REH power relays are designed for maximum performan...

View The Product Request A Quote

Contact Us

Do you need technical or commercial support?

GET A QUOTE